Global data–water symbiosis: what the first worldwide study found
A 2026 peer-reviewed study mapped every data center and municipal wastewater plant it could find and asked what would happen if they worked together. The answer: large carbon, water and cost savings, with the United States at the top of the list.
Read the paper
Global data–water symbiosis reduces AI infrastructure's carbon and water footprint
Aijie Wang, Congchao Zhang, Tiefu Xu, Dragan Savic, Jingjing Jiang, Peng Xiao, Chuan He, Yu Tao, Glen Daigger and Nanqi Ren. Environmental Science and Ecotechnology 31 (2026) 100702. Received March 13, 2026; accepted April 22, 2026. doi:10.1016/j.ese.2026.100702
The article is open access and free to read and download from the publisher, with its supplementary data. EcoVia is not affiliated with the authors or the publisher, and they have not reviewed or endorsed EcoVia or its technology.
The study in brief
Data centers need a great deal of cooling: the authors note that the average modern data center uses about 40% of its power for cooling, and much of that cooling evaporates fresh water. Wastewater plants, meanwhile, discharge large volumes of treated water that could absorb that heat. Until this study, nobody had evaluated the pairing worldwide.
The researchers built a database of 4,775 data centers and 57,547 municipal wastewater plants in 98 countries. They then used optimization and life-cycle assessment to pair facilities so that treated effluent cools each data center and the data center's heat goes back to the plant for sludge drying and anaerobic digestion. A pairing was kept only if it saved money, and the model steered away from water-stressed regions where reclaimed water is needed for other uses.
Key findings
They are already neighbors
Data centers and wastewater plants are clustered together far more than chance would predict (Moran's I = 0.67). Most treatment plants (83.5%) are in regions with an annual average temperature below 20 °C, so their water has substantial cooling capacity.
Wastewater can carry the load
The paired plants could meet nearly all of the cooling demand of the data centers in the inventory, using only about 1.64% of all treated effluent. On average, a data center's cooling water is about 3% of its partner plant's capacity, so daily plant operations are not affected.
Both sides gain
Returning data center heat to the plant cuts the energy needed for sludge drying and keeps anaerobic digesters warm. Almost all of the freshwater savings (99%) come from using treated wastewater for cooling instead of drinking-water supplies.
It pays, even over distance
Pipelines and extra treatment add cost, but the cooling savings outweigh them. Above about 21 MW of data center load, pipeline length makes little difference to the net savings, and longer links still pay.
The United States leads
The United States has the largest share of every benefit the study measured. Within the U.S., California, Texas and Illinois contribute the most.
| Country | Share of GHG mitigation | Share of freshwater savings | Annual cost savings |
|---|---|---|---|
| United States | 24.1% | 31.5% | $11.71 billion |
| Japan | 18.1% | 8.6% | $8.82 billion |
| China | 16.2% | 8.1% | $4.32 billion |
| Netherlands | 10.0% | 14.2% | $8.07 billion |
| United Kingdom | 5.9% | — | $5.02 billion |
From Wang et al. (2026), sections 3.2 and 3.3. A dash means the country is not among the five largest for that measure in the paper.
A simulated pairing in Shenzhen
Using two years of operating data from a real wastewater plant, the authors simulated a co-located data center. The data center's warm water was split three ways: into the plant's biological treatment unit, to keep the anaerobic digester warm, and to dry sludge.
- Sludge-drying energy fell by 15.4 MWh a day, a 22.7% improvement.
- Methane production rose by 6.8%.
- Cooling power at the data center fell by 6.3 MW (4.3%), and server-room temperature dropped by about 5 °C.
- The authors note that the slight temperature increase in the biological treatment unit may benefit treatment efficiency.
Practical, not just conceptual
The authors conclude that the pairing is feasible with established engineering. Corrosion, scaling and biofouling can be managed with filtration, disinfection, corrosion-resistant materials, heat exchangers that keep the water streams separate, and continuous water-quality monitoring. They suggest structuring each pairing like a district-heating agreement, with the plant supplying cooling and recovering heat and the data center as its customer, and they call on governments to fund pilot projects, remove regulatory barriers and set standards for treated water.
“WWTPs are poised to evolve from disposal facilities into critical energy-coupling hubs.” — Wang et al. (2026)
What it means for EcoVia's approach
The study shows, at global scale, that putting data centers and wastewater plants together saves carbon, water and money, and that the two are usually close enough to connect. EcoVia's pending application, U.S. provisional 64/158,951, takes the pairing in a different direction:
The study
- Treated effluent, after tertiary treatment, cools the data center.
- Returned heat goes mainly to sludge drying and digestion.
- Goal: lower carbon and water footprints.
EcoVia's application
- Human-generated sewage is the sole or primary heat sink.
- Warmed sewage returns to the aeration and anoxic basins, where warmth speeds nitrogen treatment.
- Added goal: an obligate dependence of AI infrastructure on continued human activity.
Further reading
Other published work on AI's water use, cooling with treated wastewater, and how temperature affects wastewater treatment. Links go to the publishers or authors.
- Li P., Yang J., Islam M. A., Ren S. (2025). Making AI less “thirsty”: uncovering and addressing the secret water footprint of AI models. Communications of the ACM 68(7). Projects that global AI could withdraw 4.2 to 6.6 billion m³ of water in 2027. doi:10.1145/3724499
- Chinese Academy of Sciences (May 6, 2026). Data–water symbiosis: coupling data centres with wastewater treatment plants could cut 84 million tonnes of CO2 eq and save 1,300 million m³ of freshwater annually. Newswise · EurekAlert!
- Li H., Hsieh M.-K., Chien S.-H., Monnell J. D., Dzombak D. A., Vidic R. D. (2011). Control of mineral scale deposition in cooling systems using secondary-treated municipal wastewater. Water Research 45. doi:10.1016/j.watres.2010.08.052
- Hu W., Guo Y., Tian J., Chen L. (2020). Energy and water saving potentials in industrial parks by an infrastructure-integrated symbiotic model. Resources, Conservation and Recycling. doi:10.1016/j.resconrec.2020.104992
- Heeres R. R., Vermeulen W. J. V., de Walle F. B. (2004). Eco-industrial park initiatives in the USA and the Netherlands: first lessons. Journal of Cleaner Production. doi:10.1016/j.jclepro.2004.02.014
- Szoke N. (2015). Understanding how temperature and substrate influence wastewater nitrification. Environmental Science & Engineering Magazine. esemag.com
- Wanner O. et al. (2005). Effect of heat recovery from raw wastewater on nitrification and nitrogen removal in activated sludge plants. Water Research 39(19). doi:10.1016/j.watres.2005.09.026
- IVL Swedish Environmental Research Institute. Report B2149: pilot treatment line at Hammarby Sjöstadsverk run at about 20 °C with waste heat, with higher nitrogen removal than a parallel line. IVL report (PDF)
This page summarizes published research for general information. Figures are as reported by the authors; see the paper for methods, assumptions and limitations. The summary is EcoVia's own and has not been reviewed by the authors or the publisher.